Ew =IR (F-8-3)
式中 Ew --接地裝置的電位(V);
I--計(jì)算用入地短路電流(A);
R--接地裝置(包括人工接地網(wǎng)及與其連接的所有其他自然接地體)的接地電阻(Ω)。
2.發(fā)生接地短路時(shí),接地網(wǎng)地表面的最大接觸電勢(shì),即網(wǎng)孔中心對(duì)接地網(wǎng)接地體的最大電勢(shì),可按下式計(jì)算:
Ejm= KjEw (F-8-4)
式中 Ejm--最大接觸電勢(shì)(V);
Kj--接觸系數(shù)。
當(dāng)接地體的埋設(shè)深度h=0.6~0.8m時(shí),Kj可按下式計(jì)算:
Kj=KnKdKs(F-8-5)